RE-Y(St)Y-fl & RE-Yw(St)Yw-fl MP
INSTRUMENTATION CABLES, EN 50288-7SİNGLE & MULTİ-PAİR, PVC INSULATED, COLLECTİVE SCREENED, PVC SHEATHED
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. For application of 105oC heat resistant, RE-Yw(St)Yw cables are suitable. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Outer sheath (Yw): PVC compound, 105 oC grade; EN 50290-2-22
Sheath colour: RAL 9005, Black or RAL 5015, Blue
Conductor: Plain copper wire, stranded, IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation (Y): PVC compound, 70 oC grade; EN 50290-2-21
Insulation (Yw): PVC compound, 105 oC grade; EN 50290-2-21
Core identification: Black / White cores numbered 1-1, 2-2,…, Upon request ; Colour coded according to IEC 60189-2, Other core configurations manufactured upon request.
Pair: Two conductors twisted to a pair
Lay-up: Pairs laid up in layers of optimum pitch
Separator: Polyester tape
Screen: AL-PES tape over stranded tinned copper drain, wire 0,50 mm2
Outer sheath (Y): PVC compound, 70 oC grade; EN 50290-2-22
Capacitance unbalance: (1 kHz) : max. 500 pF/500 m
Standard: TS/DIN EN 50288-7
Insulation thickness: 0,50mm2 : 0,40 mm, 0,75mm2 : 0,40 mm, 1,0mm2 : 0,40 mm, 1,3mm2 : 0,45 mm, 1,5mm2 : 0,45 mm
Conductor resistance: 0,50mm2 : 36,7 Ω/km, 0,75mm2 : 25,0 Ω/km, 1,0mm2 : 18,5 Ω/km, 1,3mm2 : 14,2 Ω/km, 1,5mm2 : 12,3 Ω/km
Insulation resistance: Min. 100 MΩ.km
L / R (ratio) (max.): 0,50mm2 : 25 µH/Ω, 0,75mm2 : 25 µH/Ω, 1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω, 1,5mm2 : 40 µH/Ω
Rated voltage: 300V
Temperature range (2Y): operation : - 30 oC ~ + 70 oC, ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X): operation : - 30 oC ~ + 105 oC, ınstallation : - 5 oC ~ + 50 oC
Min. bending radius: 7,5 x D
Flame retardance test: IEC 60332-1 & EN 60332-1